ANALISA PERBAIKAN NILAI PENTANAHAN DENGAN SISTEM COUPLING WIRE UNTUK PENANGKAL PETIR PADA JARINGAN 20KV DI PT. PLN (PERSERO) ULP TANJUNG

ERFANI, MUHAMAD RIZA (2024) ANALISA PERBAIKAN NILAI PENTANAHAN DENGAN SISTEM COUPLING WIRE UNTUK PENANGKAL PETIR PADA JARINGAN 20KV DI PT. PLN (PERSERO) ULP TANJUNG. Diploma thesis, Universitas Islam Kalimantan MAB.

[img] Text
ARTIKEL MUHAMAD RIZA ERFANI.pdf

Download (387kB)
[img] Text
ARTIKEL MUHAMAD RIZA ERFANI.pdf

Download (387kB)
[img] Text
ARTIKEL MUHAMAD RIZA ERFANI.docx

Download (90kB)
[img] Text
KEASLIAN.pdf

Download (236kB)
[img] Text
PENGESAHAN.pdf

Download (382kB)
[img] Text
ARTIKEL ABSTRAK MUHAMAD RIZA ERFANI.pdf

Download (32kB)

Abstract

Penjagaan dan pengelolaan saluran distribusi listrik dari gangguan petir dapat dilakukan dengan sistem pentanahan. Semakin kecil nilai pentanahan dari grounding tersebut maka kualitas pentanahan atau grounding akan semakin baik, dikarena arus gangguan listrik akan lebih mudah mengalir ke tanah melalui tempat yang memiliki hambatan sekecil mungkin. Oleh karena itu, penelitian ini dilakukan dengan tujuan untuk menganalisa perbaikan nilai pentanahan dengan Sistem Coupling Wire sebagai penangkal petir. Metode penelitian yang digunakan adalah penelitian eksperimen. Instrumen yang digunakan adalah coupling wire dengan menggunakan UHGW (Under Head Ground Wire) dan earth tester. Cara kerja Sistem Coupling Wire dalam melindungi saluran distribusi adalah dengan memperkecil nilai pentanahan melalui paralel UHGW antar penyulang sehingga arus listrik dari petir lebih mudah mengalir ke tanah karena hambatan yang terjadi juga diperkecil. Pengujian dilakukan di dua lokasi berbeda, yakni di Gardu Induk Tanjung dan Desa Wirang. Hasil yang didapatkan adalah nilai pentanahan pada lokasi pertama sebelum dan sesudah dipasang coupling wire adalah 3,26 ohm (tiang 1) dan 0,83 ohm (tiang 2) menjadi 0,41 ohm. Sedangkan nilai pentanahan pada lokasi kedua sebelum dan sesudah dipasang coupling wire adalah 4,8 ohm (tiang 1), 3,5 ohm (tiang 2), 8,9 ohm (tiang 3), 9,48 ohm (tiang 4), 7,6 ohm (tiang 5), dan 5,5 ohm (tiang 6), menjadi 0,9 ohm. Kesimpulan dari penelitian ini adalah bahwa Sistem Coupling Wire yang diterapkan dapat mempengaruhi nilai pentanahan dengan menurunkan nilai pentanahan sehingga saluran distribusi di PT. PLN Tanjung dapat dilindungi secara efektif dari gangguan sambaran petir. Kata Kunci : Nilai Pentanahan, Coupling Wire, UHGW, Petir, Jaringan 20 KV Maintenance and management of electricity distribution lines from lightning disturbances can be done with a grounding system. The smaller the grounding value of the grounding, the better the quality of grounding or grounding, because the electric fault current will flow more easily to the ground through a place that has the smallest possible resistance. Therefore, this research was conducted with the aim of analyzing the improvement of the grounding value with the Coupling Wire System as a lightning rod. The research method used is experimental research. The instrument used is a coupling wire using UHGW (Under Head Ground Wire) and an earth tester. The way the Coupling Wire System works in protecting distribution channels is to reduce the value of grounding through parallel UHGW between feeders so that electric current from lightning flows more easily to the ground because the resistance that occurs is also minimized. The tests were carried out in two different locations, namely at the Tanjung Substation and Wirang Village. The results obtained are the grounding values at the first location before and after the coupling wire is installed are 3.26 ohms (pole 1) and 0.83 ohms (pole 2) to 0.41 ohms. While the grounding values at the second location before and after the coupling wire is installed are 4.8 ohms (pole 1), 3.5 ohms (pole 2), 8.9 ohm (pole 3), 9.48 ohms (pole 4), 7 .6 ohms (pole 5), and 5.5 ohms (pole 6), making 0.9 ohms. The conclusion of this study is that the Coupling Wire System applied can affect the value of grounding by lowering the value of grounding so that the distribution channel at PT. PLN Tanjung can be effectively protected from lightning strikes. Keywords: Grounding Value, Coupling Wire, UHGW, Lightning, 20 KV Jaringan Network

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Nilai Pentanahan, Coupling Wire, UHGW, Petir, Jaringan 20 KV
Subjects: T Technology > TA Engineering (General). Civil engineering (General)
Depositing User: Muhamad Riza Erfani
Date Deposited: 13 Jul 2024 04:06
Last Modified: 13 Jul 2024 04:06
URI: http://eprints.uniska-bjm.ac.id/id/eprint/23962

Actions (login required)

View Item View Item